Výkonový transformátor 35 kV oleje
20000KVA 35KV
20000KVA 35KV
3150KVA 35KV
| Jmenovitá kapacita (KVA) | Kombinace napětí | Připojte se ke skupinovému štítku | Ztráta naprázdno (W) | Ztráta zatížení (W) | Zkratová impedance (%) | Proud naprázdno (%) | ||
| Vysoké napětí (KV) | Tapoff % | Nízký tlak (KV) | ||||||
| S13-50/35 | 38.5 35 | ±5 ±2x2,5 | 0.4 | Dyn11 Yyn0 | 128 | 1200/1140 | 6.5 | 1.30 |
| S13-100/35 | 184 | 2010/1910 | 1.10 | |||||
| S13-125/35 | 216 | 2370/2260 | 1.10 | |||||
| S13-160/35 | 224 | 2820/2680 | 1.00 | |||||
| S13-200/35 | 272 | 3320/3160 | 1.00 | |||||
| S13-250/35 | 320 | 3950/3760 | 0.95 | |||||
| S13-315/35 | 384 | 4750/4530 | 0.95 | |||||
| S13-400/35 | 464 | 5740/5470 | 0.85 | |||||
| S13-500/35 | 544 | 6910/6580 | 0.85 | |||||
| S13-630/35 | 664 | 7860 | 0.65 | |||||
| S13-800/35 | 784 | 9400 | 0.65 | |||||
| S13-1000/35 | 920 | 11500 | 0.65 | |||||
| S13-1250/35 | 1120 | 13900 | 0.60 | |||||
| S13-1600/35 | 1350 | 16600 | 0.60 | |||||
| S13-2000/35 | 1590 | 19700 | 0.55 | |||||
| S13-2500/35 | 1890 | 23200 | 0.55 | |||||
| Jmenovitá kapacita (KVA) | Připojte se ke skupinovému štítku | Kombinace napětí | Proud naprázdno % | Ztráta naprázdno W | Ztráta zatížení (120 ℃) W | Impedanční napětí % | ||
| Vysoké napětí (KV) | Rozsah vysokotlakého kohoutku % | Nízký tlak (KV) | ||||||
| SCB10-315/35 | Yyn0 or Dyn11 | 35 or 38.5 | ±5 nebo ±2×2,5 | 0.4 3.15 6 6.3 10 10.5 11 | 2 | 1160 | 4170 | 6 7 8 9 |
| SCB10-400/35 | 2 | 1360 | 5360 | |||||
| SCBI10-500/35 | 2 | 1600 | 6590 | |||||
| SCB10-630/35 | 1.8 | 1840 | 7680 | |||||
| SCB10-800/35 | 1.9 | 2220 | 9350 | |||||
| SC810-1000/35 | 1.9 | 2640 | 10880 | |||||
| SCB10-1250/35 | 1.7 | 3090 | 12840 | |||||
| SCB10-1600/35 | 1.7 | 3650 | 15390 | |||||
| SCB10-2000/35 | 1.5 | 4200 | 18110 | |||||
| SCB10-2500/35 | 7.5 | 4800 | 21680 | |||||
| SCB10-3150/35 | 1.3 | 5000 | 24400 | |||||
| SC810-4000/35 | 1.3 | 6950 | 29330 | |||||
| SCB10-5000/35 | 1.1 | 8320 | 34770 | |||||
| SCB10-6300/35 | 1.1 | 9840 | 40630 | |||||
| SCB10-8000/35 | Yd11 or Ynd11 | 1 | 11200 | 45050 | ||||
| SCB10-10000/35 | 1 | 12800 | 51200 | 7 | ||||
| SC810-12500/35 | 0.9 | 16150 | 55300 | |||||
| SCB10-16000/35 | 0.8 | 19560 | 59800 | |||||
1. Proces návrhu rozvodny: Fázový přístup Rozvodna 110 kV trvala 16 měsíců od konceptu po uvedení do provozu...
PŘEČTĚTE SI VÍCEVýkonový transformátor 40 MVA vypne diferenciální ochranu po poruše blízkého vývodu. Testy oleje čisté. Odpor vinu...
PŘEČTĚTE SI VÍCECo je to polovodičový transformátor (SST)? V roce 2022 evropský pilotní projekt nahradil konvenční distribuč...
PŘEČTĚTE SI VÍCEKrize nedostatku transformátorů: Proč jsou nové rostliny kritické Více než 80 % velkých výkonových transform...
PŘEČTĚTE SI VÍCE